-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Plan Review Details - Permit 22051331
Plan Review Stops For Permit 22051331
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 3 Status A Date 09-21-2022 Cont ID  
Sent By cdorman Date 09-21-2022 Time 08:39 Rev Time 0.00
Received By cdorman Date 09-01-2022 Time 07:48 Sent To  
Notes
2022-09-01 07:48:46.00000REVSIIONS FLPERMITS@VISIONSOLAR.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status D Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By cshackel Date 08-07-2022 Time 10:57 Sent To  
Notes
2022-08-09 17:05:34.00000SHEET E-4: AC CURRENT LABEL SHOULD SHOW ACTUAL INVERTER
 OUTPUT OF 47.5 AMPS PER 690.54. DO NOT ADD A 25%
 CONTINUOUS LOAD FACTOR TO THIS LABEL; CONTINUOUS LOAD
 FACTOR APPLIES TO CIRCUIT COMPONENTS ONLY PER 690.8
 (B). THIS NOTE HAS BEEN REPEATEDLY INSERTED ON THIS
 CONTRACTOR'S PREVIOUS PLAN REVIEWS.
2022-08-07 10:58:09.00000REVISED PLAND FLPERMITS@VISIONSOLAR.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status A Date 06-08-2022 Cont ID  
Sent By cdorman Date 06-08-2022 Time 15:41 Rev Time 0.00
Received By cdorman Date 05-20-2022 Time 14:59 Sent To  
Notes
2022-05-20 14:59:24.00000LONESTARPERMITTING@GMAIL.COM

Copyright © 2008 – THE PLUS SERIES ® – All Rights Reserved