-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Plan Review Details - Permit 22051302
Plan Review Stops For Permit 22051302
Review Stop BLDREN REISSUANCE BUILDING PERMIT
Rev No 1 Status A Date 02-09-2023 Cont ID  
Sent By cshackel Date 02-09-2023 Time 09:00 Rev Time 0.00
Received By cshackel Date 02-09-2023 Time 09:00 Sent To  
Notes
***NONE***

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 3 Status A Date 01-06-2023 Cont ID  
Sent By cdorman Date 01-06-2023 Time 08:37 Rev Time 0.00
Received By cdorman Date 12-15-2022 Time 14:09 Sent To  
Notes
2022-12-15 14:10:02.00000RVISONS FLPERMITS@VISIONSOLAR.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status D Date   Cont ID  
Sent By   Date 08-09-2022 Time   Rev Time 0.00
Received By cshackel Date 08-07-2022 Time 10:56 Sent To  
Notes
2022-08-09 16:55:39.00000SHEET E-4: AC CURRENT LABEL SHOULD SHOW ACTUAL INVERTER
 OUTPUT OF 25 AMPS PER 690.54. DO NOT ADD A 25%
 CONTINUOUS LOAD FACTOR TO THIS LABEL; CONTINUOUS LOAD
 FACTOR APPLIES TO CIRCUIT COMPONENTS ONLY PER 690.8
 (B). THIS NOTE HAS BEEN REPEATEDLY INSERTED ON THIS
 CONTRACTOR'S PREVIOUS PLAN REVIEWS.
2022-08-07 10:57:16.00000REVISED PLANS EMAILED IN FLPERMITS@VISIONSOLAR.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status A Date 06-08-2022 Cont ID  
Sent By cdorman Date 06-08-2022 Time 15:41 Rev Time 0.00
Received By cdorman Date 05-20-2022 Time 10:55 Sent To  
Notes
2022-05-20 10:55:51.00000LONESTARPERMITTING@GMAIL.COM

Copyright © 2008 – THE PLUS SERIES ® – All Rights Reserved