Plan Review Details - Permit 22050280
Plan Review Stops For Permit 22050280
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 3 Status A Date 08-18-2022 Cont ID  
Sent By cdorman Date 08-18-2022 Time 14:22 Rev Time 0.00
Received By cdorman Date 08-18-2022 Time 09:12 Sent To  
Notes
2022-08-18 09:12:20.00000PERMITTING@MERAKISOLUTIONS.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status D Date 06-29-2022 Cont ID  
Sent By cdorman Date 06-29-2022 Time 16:31 Rev Time 0.00
Received By cdorman Date 06-29-2022 Time 13:35 Sent To  
Notes
2022-06-29 16:31:04.00000SHEET PV05: EQUIPMENT SCHEDULE SHOWS 6 KW INVERTER
 SHEET PV06: STRING CALCULATIONS SHOW 6 KW INVERTER
 SHEET PV07: LABELS SHOW 6 KW INVERTER PARAMETERS
 COVER SHEET AND ONE-LINE DIAGRAM INDICATE A 3.8 KW
 INVERTER PROPOSED.
2022-06-29 13:35:38.00000REVISIONS REC'D APRIL.SHEDLOCK@MERAKISOLUTIONS.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 05-05-2022 Cont ID  
Sent By cdorman Date 05-05-2022 Time 15:57 Rev Time 0.00
Received By cdorman Date 05-05-2022 Time 10:10 Sent To  
Notes
2022-05-05 15:57:01.00000SHEETS PV-01, 05, & 06 SHOW CONFLICTING INFOMATION ON
 INTENDED INVERTER. BOTH 3800 WATT AND 6000 WATT
 INVERTERS ARE LISTED. CLARIFY INTENDED INVERTER,
 CONDUCTORS, AND OVERCURRENT PROTECTION.
2022-05-05 10:11:41.00000ALSO HAS ELECTRICAL PERMIT
 APRIL.SHEDLOCK@MERAKISOLUTIONS.COM