Plan Review Details - Permit 22041210
Plan Review Stops For Permit 22041210
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 3 Status A Date 12-22-2022 Cont ID  
Sent By cdorman Date 12-22-2022 Time 12:36 Rev Time 0.00
Received By cdorman Date 12-06-2022 Time 10:05 Sent To  
Notes
2022-12-05 08:59:04.0000012/05/22: UPDATED PLANS FOR REVIEW, FORWARDED TO CHUCK.
 RCVD BY EMAIL: RACHAEL HANSEN
 

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status D Date 11-17-2022 Cont ID  
Sent By cdorman Date 11-17-2022 Time 15:57 Rev Time 0.00
Received By cdorman Date 11-16-2022 Time 08:28 Sent To  
Notes
2022-11-17 15:57:43.00000REVISED PLANS, SHEET PV3: 30 AMP PV DISCONNECT IS
 UNDERSIZED FOR SYSTEM. ALL COMPONENTS MUST BE RATED AT
 A MINIMUM OF 125% OF THE COMBINED MAXIMUM INVERTER
 OUTPUT.
2022-11-16 08:29:16.00000RACHAEL@BAYAREPROJECTSOLUTIONS.COM
 REVISION

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 04-28-2022 Cont ID  
Sent By cdorman Date 04-28-2022 Time 15:31 Rev Time 0.00
Received By cdorman Date 04-28-2022 Time 07:52 Sent To  
Notes
2022-04-28 15:31:40.00000SHEET PV-5: #10 AWG CONDUCTORS BETWEEN COMBINER PANEL
 AND PV DISCONNECT ARE UNDERSIZED FOR PROPOSED O/C
 DEVICE. CHANGE THESE CONDUCTORS TO #8 AWG.
2022-04-28 07:53:11.00000EMAILED IN RICHARD@SEMPOWER.COM