-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Plan Review Details - Permit 22040228
Plan Review Stops For Permit 22040228
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 04-25-2022 Cont ID  
Sent By cdorman Date 04-25-2022 Time 15:33 Rev Time 0.00
Received By cdorman Date 04-25-2022 Time 13:09 Sent To  
Notes
2022-04-25 13:09:22.00000ADRIANAERIC96@YAHOO.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 04-11-2022 Cont ID  
Sent By cdorman Date 04-11-2022 Time 16:30 Rev Time 0.00
Received By cdorman Date 04-11-2022 Time 16:23 Sent To  
Notes
2022-04-11 16:30:01.000001] CONDUCTOR SET #1 MUST INCLUDE AN EQUIPMENT GROUNDING
 CONDUCTOR BASED ON T250.122
 2] IDENTIFY CONDUCTOR SET #4 INCLUDING EQUIPMENT
 GROUNDING CONDUCTOR
 3] INCLUDE NOTE STATING THAT GROUNDS/NEUTRALS WILL BE
 ELECTRICALLY SEPARATED IN ATS
 4] SHOW SERVICE GROUNDING ELECTRODE CONDUCTOR
 TERMINATED IN MDP, NOT IN CT METER SOCKET; SHOW SIZE OF
 THIS CONDUCTOR
 5] SHOW BOTH TRANSFORMER GROUNDING ELECTRODE CONDUCTOR
 SIZES. THESE CONDUCTORS MUST BE BASED ON THE DERIVED
 (SECONDARY) CONDUCTORS, AND SIZED PER TABLE 250.102
 (C)(1).