Plan Review Details - Permit 22030804
Plan Review Stops For Permit 22030804
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 04-19-2022 Cont ID  
Sent By cdorman Date 04-19-2022 Time 15:59 Rev Time 0.00
Received By cdorman Date 04-14-2022 Time 12:23 Sent To  
Notes
***NONE***

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 03-25-2022 Cont ID  
Sent By cdorman Date 03-25-2022 Time 15:58 Rev Time 0.00
Received By cdorman Date 03-22-2022 Time 15:18 Sent To  
Notes
2022-03-25 15:58:45.00000SHEET W001: SHOW SIZE OF BACKFED CIRCUIT BREAKER USED
 FOR PV INTERCONNECTION
 SHEET L001: REMOVE TWO AC CURRENT/VOLTAGE LABELS
 SHOWING INCORRECT CURRENT. MAXIMUM OUTPUT OF THE
 PROPOSED SYSTEM IS 22 AMPS (ROUNDED).
 SHEET L001: INCLUDE RAPID SHUTDOWN GRAPHIC LABEL PER
 NEC FIGURE 690.56 (C)(1)(A).
 REPLACE ONLY THE TWO AFFECTED SHEETS, NOT THE ENTIRE
 SET OF PLANS.