Plan Review Stops For Permit 22020811
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 04-01-2022 Cont ID  
Sent By cdorman Date 04-01-2022 Time 14:00 Rev Time 0.00
Received By cdorman Date 03-18-2022 Time 10:44 Sent To  
Notes
2022-03-18 10:45:01.00000REVISED PLANS WAS EMAILED IN ON 3/18/2022 @ 10:06AM
 FROM PERMITS@SUNVENA.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 03-09-2022 Cont ID  
Sent By cdorman Date 03-09-2022 Time 15:22 Rev Time 0.00
Received By cdorman Date 02-21-2022 Time 10:10 Sent To  
Notes
2022-03-09 15:22:26.00000SHEET E-01: CONDUCTORS BETWEEN COMBINER PANEL AND
 SUPPLY-SIDE TAP (VIA PV DISCONNECT) MUST HAVE AN
 MINIMUM AMPACITY OF 98 AMPS BASED ON 75 DEGREE C
 TERMINAL RATINGS. CHANGE THIS CONDUCTOR TO MINIMUM #3
 CU.