Rev No 3 Status A Date 05-23-2022 Cont ID  
Sent By cdorman Date 05-23-2022 Time 16:03 Rev Time 0.00
Received By cdorman Date 05-02-2022 Time 16:21 Sent To  
Notes
2022-05-02 16:21:37.00000PERMITTING@ATLANTICKEYENERGY.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status D Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By hlopez Date 04-19-2022 Time 09:46 Sent To  
Notes
2022-04-19 16:35:07.00000SHEET E2: CONDUCTORS BETWEEN COMBINER PANEL AND MAIN
 SERVICE PANEL (ID #5 & 6) MUST HAVE A MINIMUM AMPACITY
 OF 36.3 AT 75 DEGREES C. CHANGE TO MINIMUM #8 CU. SEE
 TABLE 310.15 (B)(16).
2022-04-19 09:46:30.00000PERMITTING@ATLANTICKEYENERGY.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status A Date 02-28-2022 Cont ID  
Sent By cdorman Date 02-28-2022 Time 08:24 Rev Time 0.00
Received By cdorman Date 02-17-2022 Time 08:04 Sent To  
Notes
2022-02-17 08:05:34.00000EMAILED IN FROM ATLANTICKEYENERGY.COM ON 2/16/2022 @
 5:42PM