2021-12-03 15:52:54.00000SHEET E-601, CONDUCTOR ID #2: #6 TYPE NM CABLE HAS A
 MAXIMUM AMPACITY OF 55. REFER TO 334.80 AND TABLE
 310.15 (B)(16).
 MINIMUM REQUIRED CIRCUIT AMPACITY = 60.5 (40 INVERTERS
 @ 1.21A X 1.25). CONDUCTORS MEETING THIS MINIMUM
 AMPACITY MAY BE FUSED AT 70 AMPS AS INDICATED ON PLANS.
  