Review Stop BUILDING BUILDING DEPARTMENT
Rev No 3 Status A Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By hlopez Date 10-21-2021 Time 10:54 Sent To  
Notes
***NONE***

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status D Date 10-18-2021 Cont ID  
Sent By cdorman Date 10-18-2021 Time 14:15 Rev Time 0.00
Received By cdorman Date 10-15-2021 Time 15:24 Sent To  
Notes
2021-10-18 14:14:15.00000ITEM #1 ON PREVIOUS REVIEW HAS NOT BEEN CORRECTED ON
 PLANS: SHEETS E-01 & E-02: #8 CONDUCTORS BETWEEN
 COMBINER PANEL AND INTERCONNECTION POINT ARE UNDERSIZED
 FOR 125% OF COMBINED INVERTER OUTPUTS, AND UNDERSIZED
 FOR 60 AMP OVERCURRENT PROTECTION. (34 IQ7+ INVERTERS @
 1.21 AMPS) X 1.25 = 51.4 AMPS. SEE TABLE 310.15
 (B)(16): USING 75 DEGREE COLUMN, # 8 AMPACITY = 50.
 OVERCURRENT PROTECTION FOR #8 (BASED ON 75 DEGREE
 TERMINATIONS) IS LIMITED TO 50 AMPS; 60 AMP IS REQUIRED
 FOR THIS SYSTEM. SEE 240.4 (B). USE #6 THWN CONDUCTORS
 FOR THIS APPLICATION.
  
2021-10-15 15:24:51.00000 
  
 REVISIONS 10/15/21 PERMITS@SUNVENA.COM
  
  

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 10-13-2021 Cont ID  
Sent By cdorman Date 10-13-2021 Time 16:02 Rev Time 0.00
Received By cdorman Date 10-11-2021 Time 10:12 Sent To  
Notes
2021-10-13 16:02:45.000001] SHEETS E-01 & E-02: #8 CONDUCTORS BETWEEN COMBINER
 PANEL AND INTERCONNECTION POINT ARE UNDERSIZED FOR 125%
 OF COMBINED INVERTER OUTPUTS, AND UNDERSIZED FOR 60 AMP
 OVERCURRENT PROTECTION. (34 IQ7+ INVERTERS @ 1.21 AMPS)
 X 1.25 = 51.4 AMPS. SEE TABLE 310.15 (B)(16): USING 75
 DEGREE COLUMN, # 8 AMPACITY = 50.
 OVERCURRENT PROTECTION FOR #8 (BASED ON 75 DEGREE
 TERMINATIONS) IS LIMITED TO 50 AMPS; 60 AMP IS REQUIRED
 FOR THIS SYSTEM. SEE 240.4 (B). USE #6 THWN CONDUCTORS
 FOR THIS APPLICATION.
 2] PROVIDE SPEC SHEET FOR INVERTERS
 3] PROVIDE SPEC SHEET FOR PV MODULES
 4] PROVIDE SPC SHEET FOR COMBINER PANEL
2021-10-11 10:12:21.00000APPLICAITON DROPPED OF 10/08/2021