Plan Review Stops For Permit 21100275
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status A Date 12-09-2021 Cont ID  
Sent By hlopez Date 12-09-2021 Time 08:58 Rev Time 0.00
Received By hlopez Date 10-11-2021 Time 10:24 Sent To  
Notes
2021-12-08 16:26:49.00000CHARLES REVIEWED THE ELECTRICAL TODAY AND THIS IS HIS
 COMMENT: ELECTRICAL LAYOUT LOOKS OK; THE FOLLOWING
 LANGUAGE SHOULD BE ADDED TO SHEETS E-101 & E-102, OR
 INCLUDED IN REVIEW COMMENTS:
 "ALL BRANCH CIRCUITS SERVING PATIENT CARE SPACES SHALL
 COMPLY WITH THE EQUIPMENT GROUNDING PROVISIONS OF NFPA
 70, SECTION 517.13"
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status A Date   Cont ID  
Sent By   Date 11-24-2021 Time 3:08 Rev Time 0.00
Received By hlopez Date 10-11-2021 Time 10:25 Sent To  
Notes
2021-11-24 15:08:46.00000PLANS AND ALL DOCUMENTS ON G: DRIVE