Plan Review Details - Permit 21100198
Plan Review Stops For Permit 21100198
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 4 Status A Date 01-19-2022 Cont ID  
Sent By cdorman Date 01-19-2022 Time 16:00 Rev Time 0.00
Received By cdorman Date 01-10-2022 Time 08:54 Sent To  
Notes
2022-01-10 08:55:01.00000ANOTHER REVISION - PERMMITTING@MERAKISOLUTIONS.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 3 Status A Date 11-29-2021 Cont ID  
Sent By cdorman Date 11-29-2021 Time 15:48 Rev Time 0.00
Received By cdorman Date 11-15-2021 Time 15:25 Sent To  
Notes
2021-11-15 15:25:22.00000ANOTHER REVISION PERMITTING@MERAKISOLUTIONS.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 10-21-2021 Cont ID  
Sent By cdorman Date 10-21-2021 Time 08:16 Rev Time 0.00
Received By cdorman Date 10-14-2021 Time 08:31 Sent To  
Notes
2021-10-14 08:31:33.00000REVISIONS 10/13/21 PERMITTING@MERAKISOLUTIONS.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 10-07-2021 Cont ID  
Sent By cdorman Date 10-07-2021 Time 15:53 Rev Time 0.00
Received By cdorman Date 10-07-2021 Time 10:09 Sent To  
Notes
2021-10-07 15:53:27.00000SHEET PV-05: SHOW DISCONNECTING MEANS/OVERCURRENT
 PROTECTION ON SUPPLY-SIDE OF COMBINER PANEL.
 DISCONNECTING MEANS SUPPLIED BY A LINE-SIDE TAP MUST BE
 LISTED SUITABLE FOR SERVICE EQUIPMENT (690.13 C), MUST
 HAVE A SHORT CIRCUIT RATING AT LEAST EQUAL TO THE
 AVAILAIBLE SERVICE SHORT CIRCUIT CURRENT (690.13 E),
 AND MUST BE LOCKABLE IN THE OPEN POSITION (705.22, ITEM
 7). IT CANNOT BE DETERMINED THAT THE INTENDED COMBINER
 PANEL MEETS THESE CONDITIONS.
2021-10-07 10:09:46.00000PERMITTING@MERAKISOLUTIONS.COM