Plan Review Stops For Permit 21100001
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 11-01-2021 Cont ID  
Sent By cdorman Date 11-01-2021 Time 12:35 Rev Time 0.00
Received By cdorman Date 10-26-2021 Time 15:24 Sent To  
Notes
2021-10-26 15:24:57.00000EMAILED IN FROM BBPERMITTINGSERVICES@GMAIL.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 10-04-2021 Cont ID  
Sent By cdorman Date 10-04-2021 Time 14:49 Rev Time 0.00
Received By cdorman Date 10-01-2021 Time 12:01 Sent To  
Notes
2021-10-04 14:49:46.00000SHEET A-103: SHOW COMPLIANCE WITH FLORIDA FIRE
 PREVENTION CODE 11.12.2.2.1 & 11.12.2.2.2.2: FOR EACH
 ROOF PLANE WITH A PV ARRAY, A 36" WIDE PATHWAY FROM
 GUTTER TO RIDGE SHALL BE PROVIDED . . . . FOR PV ARRAYS
 OCCUPYING MORE THAN 33% OF THE PLAN VIEW ROOF AREA, A
 MINIMUM 36" PATHWAY WHALL BE PROVIDED ON EITHER SIDE OF
 THE RIDGE.
2021-10-01 12:01:54.00000EMAILED IN BY BBPERMITTINGSERVICES@GMAIL.COM