Plan Review Stops For Permit 21090792
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 4 Status A Date 01-19-2022 Cont ID  
Sent By cdorman Date 01-19-2022 Time 16:04 Rev Time 0.00
Received By cdorman Date 01-10-2022 Time 12:43 Sent To  
Notes
2022-01-10 12:44:09.00000REVISION ON PLANS DROPPED OFF ON 1/10/22

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 3 Status D Date 12-20-2021 Cont ID  
Sent By cdorman Date 12-20-2021 Time 16:20 Rev Time 0.00
Received By cdorman Date 12-17-2021 Time 16:22 Sent To  
Notes
2021-12-20 16:20:20.000001] NEW 200A SERVICE DISCONNECT (ADJACENT TO METER) MUST
 SHOW NEUTRAL-TO-GROUND BOND.
 2] REMOVE NEUTRAL-TO-GROUND BOND IN ENPHASE SMART
 SWITCH.
 3] A NEUTRAL CONDUCTOR IS REQUIRED ON THE UTILITY SIDE
 OF BOTH COMBINER PANELS TO OPERATE THE ENVOY. SIZE
 NEUTRALS PER TABLE 250.102 (C)(1). MINIMUM #8 CU
 REQUIRED.
 4] AT THE PV DISCONNECT CONNECTED TO THE ENPHASE SMART
 SWITCH, INCLUDE A NOTE INDICATING THAT THE NEUTRAL IS
 NOT TO BE BONDED TO THE ENCLOSURE.
 5] AT THE PV DISCONNECT CONNECTED TO THE SUPPLY-SIDE
 TAP, INCLUDE A NOTE INDICATING THAT THE NEUTRAL IS TO
 BE BONDED TO THE ENCLOSURE. A SEPARATE EQUIPMENT
 GROUNDING CONDUCTOR BETWEEN THE SERVICE AND THIS
 DISCONNECT IS NOT REQUIRED; BONDING TO EARTH IS
 ACCOMPLISHED BY THE NEUTRAL CONDUCTOR.
 5] THE STANDBY LOADS PANEL IS LABELED AS "100A", BUT
 CONTAINS A 200A MAIN BREAKER. PLEASE CLARIFY.
2021-12-17 16:22:12.00000REVISION DROPPED OFF

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 10-20-2021 Cont ID  
Sent By cdorman Date 10-20-2021 Time 14:35 Rev Time 0.00
Received By cdorman Date 10-20-2021 Time 12:20 Sent To  
Notes
2021-10-20 12:20:02.00000DROPPED OF REVISED PLANS ON 10/20/2021

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 09-28-2021 Cont ID  
Sent By cdorman Date 09-28-2021 Time 16:21 Rev Time 0.00
Received By cdorman Date 09-28-2021 Time 12:27 Sent To  
Notes
2021-09-28 16:21:04.00000SHEET E-1: #3 CONDUCTORS BETWEEN ENPHASE SMART SWITCH
 AND EXISTING PANEL ARE INCORRECTLY SIZED FOR THE 200
 AMP OVERCURRENT PROTECTION INDICATED.