Plan Review Details - Permit 21090367
Plan Review Stops For Permit 21090367
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By cshackel Date 02-22-2022 Time 14:31 Sent To  
Notes
2022-02-22 14:31:28.00000REVISED PLANS & PICS SENT IN DOREEN@LUNEXPOWER.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 10-11-2021 Cont ID  
Sent By cdorman Date 10-11-2021 Time 08:44 Rev Time 0.00
Received By cdorman Date 10-05-2021 Time 07:48 Sent To  
Notes
2021-10-05 07:49:15.00000RCVD REVISED PLANS VIA EMAIL JAIMIE@LUNEXPOWER.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 09-16-2021 Cont ID  
Sent By cdorman Date 09-16-2021 Time 13:29 Rev Time 0.00
Received By cdorman Date 09-14-2021 Time 14:35 Sent To  
Notes
2021-09-16 13:28:49.00000SHEETS PV-04 & PV-05: #10 CONDUCTORS BETWEEN COMBINER
 PANEL AND PV DISCONNECT CANNOT BE FUSED AT 40 AMPS.
 LIMIT OVERCURRENT PROTECTION TO 35 AMPS (75 DEGREE
 RATING, NEXT HIGHER SIZE OCPD ABOVE REQUIRED MCA OF
 31.76) OR CHANGE CONDUCTORS TO #8 COPPER IF USING 40
 AMP FUSE.
2021-09-14 14:35:17.00000JAIMIE@LUNEXPOWER.COM