-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Plan Review Details - Permit 21090256
Plan Review Stops For Permit 21090256
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 09-27-2021 Cont ID  
Sent By cdorman Date 09-27-2021 Time 16:39 Rev Time 0.00
Received By cdorman Date 09-22-2021 Time 15:28 Sent To  
Notes
2021-09-22 15:29:20.00000SCGRAY@FREEDOMFOREVER.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 09-16-2021 Cont ID  
Sent By cdorman Date 09-16-2021 Time 12:35 Rev Time 0.00
Received By cdorman Date 09-10-2021 Time 08:24 Sent To  
Notes
2021-09-16 12:35:06.00000SHEET PV-4: CHANGE CONDUCTORS BETWEEN INVERTER AND PV
 DISCONNECT TO MINIMUM #6 CU. (REQUIRED MCA = 52.5 WITH
 60A OCPD, #8 AS SHOWN MAX AMPACITY @ 75 DEGREES C IS
 50).
2021-09-10 08:24:28.00000SCGRAY@FREEDOMFOREVER.COM

Copyright © 2008 – THE PLUS SERIES ® – All Rights Reserved