Plan Review Details - Permit 21090217
Plan Review Stops For Permit 21090217
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 3 Status A Date 12-07-2021 Cont ID  
Sent By cdorman Date 12-07-2021 Time 15:16 Rev Time 0.00
Received By cdorman Date 11-29-2021 Time 08:55 Sent To  
Notes
2021-11-29 08:56:40.00000DROPPED OFF REVISED PLANS ON 11/24/2021

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 09-29-2021 Cont ID  
Sent By cdorman Date 09-29-2021 Time 15:57 Rev Time 0.00
Received By cdorman Date 09-21-2021 Time 15:30 Sent To  
Notes
2021-09-21 15:30:46.00000BROUGHT IN REVISED PLANS AND NOTES 9/21/21

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 09-09-2021 Cont ID  
Sent By cdorman Date 09-09-2021 Time 16:30 Rev Time 0.00
Received By cdorman Date 09-09-2021 Time 09:28 Sent To  
Notes
2021-09-09 16:30:18.00000SHEET PV-2. PROPOSED ROOF LAYOUT NOT COMPLIANT WITH
 FLORIDA FIRE PREVENTION CODE 11.12.2.2.2.2: "FOR PV
 ARRAYS OCCUPYING MORE THAN 33% OF THE PLAN VIEW ROOF
 AREA, A MINIMUM OF 36 INCH PATHWAY SHALL BE PROVIDED ON
 EITHER SIDE OF A HORIZONTAL RIDGE". ARRAY SECTION R1 OR
 R2 MUST BE MOVED AWAY FROM RIDGE TO PROVIDE
 REQUIRED PATHWAY ON EITHER SIDE OF RIDGE.
2021-09-09 09:28:40.00000APP & PLANS DROPPED OFF FOR REVIEW