-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Plan Review Details - Permit 21090061
Plan Review Stops For Permit 21090061
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 09-21-2021 Cont ID  
Sent By cdorman Date 09-21-2021 Time 08:29 Rev Time 0.00
Received By cdorman Date 09-14-2021 Time 14:42 Sent To  
Notes
2021-09-14 14:43:14.00000RECEIVED REVISED PLANS VIA EMAIL.
 DEANN.LOSSING@SUNTUITY.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 09-02-2021 Cont ID  
Sent By cdorman Date 09-02-2021 Time 13:16 Rev Time 0.00
Received By cdorman Date 09-02-2021 Time 11:45 Sent To  
Notes
2021-09-02 13:16:19.00000THIS IS AN ALTERATION TO AN EXISTING PV SYSTEM
 INSTALLED UNDER PERMIT #20080288; APPARENTLY FOR THE
 PURPOSE OF ADDING AN ENERGY STORAGE SYSTEM.
 1] PROVIDE SOLAR PERMIT APPLICATION STATING EXACT SCOPE
 OF ALTERATIONS. ELECTRICAL ALTERATION PERMIT NOT
 APPROVED.
 2] SHEET PV-2.0: CONDUCTOR LABEL C1 (#2 COPPER) HAS
 INSUFFICIENT AMPACITY FOR THE CONNECTED OVERCURRENT
 PROTECTION.

Copyright © 2008 – THE PLUS SERIES ® – All Rights Reserved