Plan Review Stops For Permit 21090049
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 4 Status A Date 11-09-2021 Cont ID  
Sent By cdorman Date 11-09-2021 Time 15:54 Rev Time 0.00
Received By cdorman Date 11-04-2021 Time 15:02 Sent To  
Notes
2021-11-04 15:49:16.00000REVISIONS & VALUATION EMAILED JAIMIE@LUNEXPOWER.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 3 Status D Date 10-29-2021 Cont ID  
Sent By cdorman Date 10-29-2021 Time 14:58 Rev Time 0.00
Received By cdorman Date 10-29-2021 Time 13:36 Sent To  
Notes
2021-10-29 14:58:37.00000REVISION ADDING ENERGY STORAGE, SHEET PV-04.2:
 1] SUPPLY-SIDE TAP CONDUCTORS MUST TERMINATE IN AN
 OVERCURRENT DEVICE THAT LIMITS CURRENT TO THE CONDUCTOR
 AMPACITY. SHOW MAIN BREAKER IN ENPHASE SMART SWITCH OR
 OTHER OVERCURRENT PROTECTION FOR THESE CONDUCTORS. IF
 USING #2 AWG AS SHOWN, PROTECTION CANNOT EXCEED 110
 AMPS.
 2] CONDUCTORS SUPPLYING CRITICAL LOADS PANEL MUST HAVE
 OVERCURRENT PROTECTION NOT EXCEEDING THEIR AMPACITY. #3
 AWG SHOWN ON PLANS HAS A MAXIMUM ALLOWABLE AMPACITY OF
 100 AMPS.
2021-10-29 13:37:02.00000JAIMIE@LUNEXPOWER.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 09-27-2021 Cont ID  
Sent By cdorman Date 09-27-2021 Time 08:08 Rev Time 0.00
Received By cdorman Date 09-17-2021 Time 12:16 Sent To  
Notes
2021-09-17 12:16:41.00000REVISION SENT IN 9/17/21 JAIMIE@LUNEXPOWER.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 09-02-2021 Cont ID  
Sent By cdorman Date 09-02-2021 Time 12:41 Rev Time 0.00
Received By cdorman Date 09-02-2021 Time 09:32 Sent To  
Notes
2021-09-02 12:41:50.000001] SHEET PV-02: NOTE 3 REFERENCES "CONDUIT ON ROOF";
 PLAN STATES THAT THE GARAGE IS REMOTE FROM THE HOUSE.
 PLEASE CLARIFY IF SEPARATE BUILDING OR IF CONNECTED
 STRUCTURALLY.
 2] SHEETS PV-02 THROUGH PV-05: ASSUMING THAT THE REMOTE
 GARAGE IS A SEPARATE STRUCTURE, SHOW A GROUNDING
 ELECTRODE SYSTEM CONNECTED TO THE EQUIPMENT GROUNDING
 SYSTEM OF THE GARAGE ARRAY. SHOW ALSO A PV
 DISCONNECTING MEANS (CAN BE NON-FUSED) AT A READILY
 ACCESSIBLE LOCATION ON THE GARAGE. IT MUST BE
 PERMANENTLY LABELED AS A PV DISCONNECTING MEANS FOR THE
 GARAGE ARRAY.
2021-09-02 09:32:55.00000GOSOLAR@LUNEXPOWER.COM