Plan Review Details - Permit 21090041
Plan Review Stops For Permit 21090041
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 10-11-2021 Cont ID  
Sent By cdorman Date 10-11-2021 Time 08:44 Rev Time 0.00
Received By cdorman Date 10-05-2021 Time 07:50 Sent To  
Notes
2021-10-05 07:50:49.00000RCVD REVISED PLANS VIA EMAILE JAIMIE@LUNEXPOWER.COM
  

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 09-02-2021 Cont ID  
Sent By cdorman Date 09-02-2021 Time 12:11 Rev Time 0.00
Received By cdorman Date 09-01-2021 Time 14:55 Sent To  
Notes
2021-09-02 12:10:55.00000SHEETS PV-04 & PV-05: OVERCURRENT DEVICES RATED 55 AMPS
 ARE NOT MANUFACTURED AS A STANDARD NEC SIZE. SEE TABLE
 240.6 (A). FUSE RATING MUST BE 60 AMPS; RETAIN USE OF
 #6 CONDUCTORS.