Plan Review Details - Permit 21080997
Plan Review Stops For Permit 21080997
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 4 Status A Date 11-15-2021 Cont ID  
Sent By cdorman Date 11-15-2021 Time 12:49 Rev Time 0.00
Received By cdorman Date 11-08-2021 Time 10:59 Sent To  
Notes
***NONE***

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 3 Status D Date 11-03-2021 Cont ID  
Sent By cdorman Date 11-03-2021 Time 16:00 Rev Time 0.00
Received By cdorman Date 11-03-2021 Time 13:18 Sent To  
Notes
2021-11-03 16:00:23.00000SENT SAME PLANS AS PREVIOUS SUBMITTAL; NO CORRECTIONS
 MADE. SEE REVIEW COMMENT FROM 9/21/21.
2021-11-03 13:18:48.00000REVISION 11/3/21
 JAIMIE@LUNEXPOWER.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status D Date 09-21-2021 Cont ID  
Sent By cdorman Date 09-21-2021 Time 16:30 Rev Time 0.00
Received By cdorman Date 09-17-2021 Time 10:42 Sent To  
Notes
2021-09-21 16:29:51.00000SHEETS PV-04 & 05: 125% OF COMBINED PV AND ENERGY
 STORAGE INPUT PLUS 175A MAIN BREAKER RATING EXCEEDS
 120% OF 200A BUS RATING. THE POSSIBILITY OF BOTH
 BATTERIES AND THE ARRAY EXPORTING TO UTILITY (WITH
 UTILITY POWER ON) IS ASSUMED. IS A SUPPLY-SIDE TAP
 POSSIBLE?
2021-09-17 10:42:28.00000RECEIVED REVISED PLANS JAIMEIE@LUNEXPOWER.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 09-02-2021 Cont ID  
Sent By cdorman Date 09-02-2021 Time 11:57 Rev Time 0.00
Received By cdorman Date 08-31-2021 Time 16:28 Sent To  
Notes
2021-09-02 11:57:45.000001] SHEETS PV-04 & PV-05: 40 AMP PV BREAKER IN
 SMARTSWITCH IS UNDERSIZED, AND SHOULD BE INCREASED TO
 50 AMP RATING. 31 MICROINVERTERS @ 1.21 AMPS X 1.25 =
 46.88 AMPS.
 2] SHEETS PV-04 & PV-05: CLARIFY IF SERVICE PANEL IS A
 FEED-THROUGH TYPE. IF SO, THE TOTAL RATING OF ALL
 OVERCURRENT DEVICES (EXCLUDING THE MAIN) MUST NOT
 EXCEED THE AMPACITY OF THE BUSBAR. IN SUCH CASE, A
 PERMANENT LABEL SHALL BE ATTACHED PER 705.12
 (B)(2)(C)(3). IF NOT A FEED-THROUGH TYPE PANEL, THE
 PV/POWER STORAGE INPUT CANNOT BE MADE AS A LOAD-SIDE
 TAP BECAUSE THE TOTAL POWER SOURCE INPUTS EXCEED 120%
 OF THE BUSBAR RATING.
2021-08-31 16:28:29.00000EMAILED IN FROM GOSOLAR@LUNEXPOWER.COM