Plan Review Details - Permit 21080537
Plan Review Stops For Permit 21080537
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 4 Status A Date 01-19-2022 Cont ID  
Sent By cdorman Date 01-19-2022 Time 15:59 Rev Time 0.00
Received By cdorman Date 01-10-2022 Time 14:26 Sent To  
Notes
2022-01-10 14:27:18.00000REVISED PLANS WAS EMAILED IN ON MONDAY 1/10/2022 @
 2:24PM FROM SSTACKHOUSE@THEPROCOMPANIES.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 3 Status D Date 12-27-2021 Cont ID  
Sent By cdorman Date 12-27-2021 Time 15:09 Rev Time 0.00
Received By cdorman Date 12-27-2021 Time 09:42 Sent To  
Notes
2021-12-27 15:09:35.00000PLANS INDICATE 27 MODULES AND 3 STRINGS; ONE-LINE
 DIAGRAM SHOWS 18 MODULES AND 2 STRINGS. PLEASE CLARIFY.
2021-12-27 09:42:56.00000ASTACKHOUSE@THEPROCOMPANIES.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date   Cont ID  
Sent By   Date 08-25-2021 Time   Rev Time 0.00
Received By hlopez Date 08-24-2021 Time 15:08 Sent To  
Notes
***NONE***

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 08-17-2021 Cont ID  
Sent By cdorman Date 08-17-2021 Time 16:15 Rev Time 0.00
Received By cdorman Date 08-17-2021 Time 08:22 Sent To  
Notes
2021-08-17 16:15:30.00000SHEET E601: WITH SUPPLY-SIDE TAP, PV DISCONNECT MUST
 PROVIDE OVERCURRENT PROTECTION, MUST BE LISTED FOR USE
 AS SERVICE EQUIPMENT, AND MUST SHOW NEUTRAL-TO-GROUND
 BONDING.
2021-08-17 08:23:48.00000SSTACKHOUSE@THEPROCOMPANIES.COM