Plan Review Details - Permit 21080411
Plan Review Stops For Permit 21080411
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 09-15-2021 Cont ID  
Sent By cdorman Date 09-15-2021 Time 14:44 Rev Time 0.00
Received By cdorman Date 09-08-2021 Time 15:16 Sent To  
Notes
2021-09-08 15:16:41.00000REVISIONS GOSOLAR@LUNEXPOWER.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 08-12-2021 Cont ID  
Sent By cdorman Date 08-12-2021 Time 15:31 Rev Time 0.00
Received By cdorman Date 08-12-2021 Time 11:39 Sent To  
Notes
2021-08-12 15:31:34.00000SHEETS PV-04 & PV-05: #10 CONDUCTORS FROM COMBINER
 PANEL TO PV DISCONNECT NOT APPROVED; CANNOT BE FUSED AT
 40 AMPS. REFER TO TABLE 310.15 (B)(16) AND 240.4 (D);
 NO EXCEPTION ALLOWED BY 240.4 (G). CHANGE CONDUCTOR
 SIZE TO #8 CU.
2021-08-12 11:40:08.00000GOSOLAR@LUNEXPOWER.COM