Plan Review Details - Permit 21080095
Plan Review Stops For Permit 21080095
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 08-11-2021 Cont ID  
Sent By cdorman Date 08-11-2021 Time 14:31 Rev Time 0.00
Received By cdorman Date 08-11-2021 Time 14:02 Sent To  
Notes
2021-08-11 14:02:35.00000REVISIONS SENT IN 8/11

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 08-03-2021 Cont ID  
Sent By cdorman Date 08-03-2021 Time 16:24 Rev Time 0.00
Received By cdorman Date 08-03-2021 Time 12:23 Sent To  
Notes
2021-08-11 14:01:55.00000REVISIONS SENT IN 8/11
2021-08-03 16:23:58.00000SHEET PV-04: EQUIPMENT GROUNDING CONDUCTOR BETWEEN
 COMBINER PANEL AND PV DISCONNECT MUST BE MINIMUM #8 CU
 (TABLE 250.122). WHEN USING SUPPLY-SIDE TAP, BOND
 NEUTRAL TO PV DISCONNECT ENCLOSURE AND DO NOT INSTALL
 SEPARATE EQUIPMENT GROUNDING CONDUCTOR BETWEEN PV
 DISCONNECT AND SERVICE PANEL.
  