Plan Review Details - Permit 21070647
Plan Review Stops For Permit 21070647
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 08-16-2021 Cont ID  
Sent By cdorman Date 08-16-2021 Time 08:27 Rev Time 0.00
Received By cdorman Date 08-10-2021 Time 10:38 Sent To  
Notes
***NONE***

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By cdorman Date 07-21-2021 Time 16:16 Sent To  
Notes
2021-07-21 16:18:44.00000SHEETS PV-04 & PV-05: #10 AWG CONDUCTOR BETWEEN
 COMBINER PANEL AND PV DISCONNECT MUST BE FUSED AT NOT
 MORE THAN 75 DEGREE C AMPACITY. USE 35 AMP FUSES OR
 REPLACE CONDUCTORS WITH MINIMUM #8 AWG.