Plan Review Details - Permit 21070595
Plan Review Stops For Permit 21070595
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 3 Status A Date 07-27-2021 Cont ID  
Sent By cdorman Date 07-27-2021 Time 13:59 Rev Time 0.00
Received By cdorman Date 07-27-2021 Time 13:58 Sent To  
Notes
***NONE***

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status D Date 07-21-2021 Cont ID  
Sent By cdorman Date 07-21-2021 Time 14:59 Rev Time 0.00
Received By cdorman Date 07-21-2021 Time 08:10 Sent To  
Notes
2021-07-21 14:59:37.000001] SHEET E-01, WIRE TAG #2: ADJUSTED/CORRECTED AMPACITY
 OF #10 CONDUCTOR (IN RACEWAY ON ROOFTOP) IS LESS THAN
 125% OF COMBINED INVERTER OUTPUT. USE HIGHER AMPACITY
 CONDUCTOR OR DIVIDE INVERTER STRINGS INTO MORE THAN ONE
 RACEWAY. SEE 690.8 (A)(3), SUBJECT TO 690.8 (B)(1) &
 (2).
 2] PLANS STILL DO NOT SHOW RAPID SHUTDOWN COMPLIANCE
 GRAPHIC LABEL PER FIGURE 690.56 (C)(1)(A).
  
  

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 07-20-2021 Cont ID  
Sent By cdorman Date 07-20-2021 Time 15:38 Rev Time 0.00
Received By cdorman Date 07-20-2021 Time 15:33 Sent To  
Notes
2021-07-20 15:37:59.000001] PLANS DO NOT INDICATE COMPLIANCE WITH FLORIDA FIRE
 PREVENTION CODE SECTION 11.12.2.2.2. ROOF LAYOUT MUST
 SHOW FIRE ACCESS PATHWAYS AND TOTAL PERCENTAGE OF ROOF
 AREA COVERED BY ARRAY(S).
 2] ADD RAPID SHUTDOWN COMPLIANCE GRAPHIC LABEL PER
 690.56. THIS LABEL SHOULD BE SHOWN WITH APPLICATION
 INSTRUCTIONS ON SHEET E-03.