-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Plan Review Details - Permit 21070426
Plan Review Stops For Permit 21070426
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 08-18-2021 Cont ID  
Sent By cdorman Date 08-18-2021 Time 15:33 Rev Time 0.00
Received By cdorman Date 08-17-2021 Time 16:45 Sent To  
Notes
2021-08-17 16:45:44.00000RECEIVED TWO SETS OF REVISED PLANS IN THE MAIL
 08/17/20212

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 07-19-2021 Cont ID  
Sent By cdorman Date 07-19-2021 Time 08:35 Rev Time 0.00
Received By cdorman Date 07-16-2021 Time 08:52 Sent To  
Notes
2021-07-19 14:51:34.00000CONTACT BART AT BART.SIMON@TOWEQUEST.COM
2021-07-19 08:35:21.00000SHEET E-2: #1 AWG CONDUCTORS FROM GENERATOR TO ATS ARE
 UNDERSIZED FOR 200 AMP OVERCURRENT PROTECTION ONBOARD
 GENERATOR

Review Stop ZONING ZONING DEPARTMENT
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By cshackel Date 07-15-2021 Time 09:57 Sent To  
Notes
2021-07-15 09:58:22.00000PACKAGE WAS MAILED IN, NEEDS CITY OF AVON PARK ZONING
 APPROVAL.

Copyright © 2008 – THE PLUS SERIES ® – All Rights Reserved