Plan Review Details - Permit 21070160
Plan Review Stops For Permit 21070160
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 5 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By hlopez Date 07-29-2021 Time 10:36 Sent To  
Notes
2021-07-29 10:36:20.00000SENT REVISED PLANS AGAIN

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 4 Status D Date 07-22-2021 Cont ID  
Sent By cdorman Date 07-22-2021 Time 14:25 Rev Time 0.00
Received By cdorman Date 07-22-2021 Time 10:55 Sent To  
Notes
2021-07-22 14:25:43.00000ORIGINAL PLANS RECEIVED AGAIN, NO CORRECTIONS MADE.

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 3 Status D Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By hlopez Date 07-16-2021 Time 12:43 Sent To  
Notes
2021-07-19 08:18:49.00000CONTRACTOR SUBMITTED IDENTICAL PLANS AS PREVIOUS;
 REQUESTED CORRECTION NOT MADE.

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status D Date 07-14-2021 Cont ID  
Sent By cdorman Date 07-14-2021 Time 12:20 Rev Time 0.00
Received By cdorman Date 07-13-2021 Time 15:56 Sent To  
Notes
2021-07-14 12:20:25.00000NEW PLANS SUBMITTED IN RESPONSE TO DISAPPROVAL; NO
 CORRECTIONS MADE TO PLANS, SAME ISSUES EXIST.
2021-07-13 15:57:12.00000GOSOLAR@LUNEXPOWER.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date 07-08-2021 Time   Sent To  
Notes
2021-07-08 16:15:31.00000EMAILED IN FROM GOSOLAR@LUNEXPOWER.COM
2021-07-08 15:35:23.00000SHEETS PV-04 & PV-05: CONDUCTORS BETWEEN COMBINER PANEL
 AND PV DISCONNECT MUST HAVE A MINIMUM AMPACITY OF 125%
 OF COMBINED INVERTER OUTPUT (34 X 1.21 X 1.25 = 51.4).
 #8 AMPACITY @ 75 DEGREES C IS 50; EQUIPMENT TERMINAL
 TEMPERATURE RATING 75 DEGREES C. INCREASE CONDUCTOR
 SIZE TO #6.