2021-07-14 13:06:52.00000SAME PLANS
  

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 07-19-2021 Cont ID  
Sent By cdorman Date 07-19-2021 Time 08:43 Rev Time 0.00
Received By cdorman Date 07-08-2021 Time 15:53 Sent To  
Notes
***NONE***

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status R Date 07-06-2021 Cont ID  
Sent By cdorman Date 07-06-2021 Time 14:45 Rev Time 0.00
Received By cdorman Date 07-06-2021 Time 10:05 Sent To  
Notes
2021-07-06 14:45:44.000001] SPECIFY TYPE OR OCCUPANCY OR PURPOSE OF BUILDING
 THAT PV MODULES WILL BE INSTALLED ON. IF USED AS
 DWELLING UNIT, FLORIDA FIRE PREVENTION CODE SECTION
 11.12.2.2 APPLIES REGARDING FIRE ACCESS PATHWAYS AND
 ROOF ACCESS POINTS.
 2] SHOW INSTALLATION OF A GROUNDING ELECTRODE SYSTEM
 CONNECTED TO THE ARRAY FRAME AT THE REMOTE BUILDING PER
 690.47.
 NOTE THAT THIS INSTALLATION WILL REQUIRE AN INSPECTION
 OF UNDERGROUND CONDUITS, EITHER BY SITE VISIT OR
 INSPECTION TUBES.