-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Plan Review Details - Permit 21070077
Plan Review Stops For Permit 21070077
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 3 Status X Date   Cont ID  
Sent By   Date 07-14-2021 Time   Rev Time 0.00
Received By hlopez Date 07-13-2021 Time 15:49 Sent To  
Notes
2021-07-14 13:06:24.00000SAME PLAN

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 07-19-2021 Cont ID  
Sent By cdorman Date 07-19-2021 Time 08:42 Rev Time 0.00
Received By cdorman Date 07-08-2021 Time 16:12 Sent To  
Notes
2021-07-08 16:13:06.00000GOSOLAR@LUNEXPOWER.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 07-06-2021 Cont ID  
Sent By cdorman Date 07-06-2021 Time 14:28 Rev Time 0.00
Received By cdorman Date 07-06-2021 Time 10:03 Sent To  
Notes
2021-07-06 14:28:07.000001] SHEETS PV-04 & PV-05: CONDUCTORS BETWEEN COMBINER
 PANEL AND PV DISCONNECT MUST HAVE A MINIMUM AMPACITY OF
 125% OF COMBINED INVERTER OUTPUT (34 X 1.21 X 1.25 =
 54.1). #8 AMPACITY @ 75 DEGREES C IS 50; EQUIPMENT
 TERMINAL TEMPERATURE RATING 75 DEGREES C. INCREASE
 CONDUCTOR TO #6.
 2] SHEETS PV-04 & PV-05: PV DISCONNECT PARAMETERS DO
 NOT MATCH.
2021-07-06 10:03:38.00000GOSOLAR@LUNEXPOWER.COM

Copyright © 2008 – THE PLUS SERIES ® – All Rights Reserved