Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Plan Review Details - Permit 21070076
Plan Review Stops For Permit 21070076
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 3 Status X Date   Cont ID  
Sent By   Date 07-14-2021 Time   Rev Time 0.00
Received By hlopez Date 07-13-2021 Time 15:47 Sent To  
Notes
2021-07-14 13:05:34.00000SENT SAME PLAN

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 07-19-2021 Cont ID  
Sent By cdorman Date 07-19-2021 Time 08:42 Rev Time 0.00
Received By cdorman Date 07-08-2021 Time 16:11 Sent To  
Notes
***NONE***

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 07-06-2021 Cont ID  
Sent By cdorman Date 07-06-2021 Time 14:24 Rev Time 0.00
Received By cdorman Date 07-06-2021 Time 10:00 Sent To  
Notes
2021-07-06 14:23:57.00000SHEETS PV-04 & PV-05: CONDUCTORS BETWEEN COMBINER PANEL
 AND PV DISCONNECT MUST HAVE A MINIMUM AMPACITY OF 125%
 OF COMBINED INVERTER OUTPUT (24 X 1.21 X 1.25 = 36.3).
 #10 AMPACITY @ 75 DEGREES C IS 35; EQUIPMENT TERMINAL
 TEMPERATURE RATING 75 DEGREES C. INCREASE CONDUCTOR TO
 #8.