Plan Review Stops For Permit 21070036
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 07-28-2021 Cont ID  
Sent By cdorman Date 07-28-2021 Time 15:24 Rev Time 0.00
Received By cdorman Date 07-28-2021 Time 08:59 Sent To  
Notes
2021-07-28 08:58:56.00000REC'D REVISED PLANS

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 07-02-2021 Cont ID  
Sent By cdorman Date 07-02-2021 Time 15:15 Rev Time 0.00
Received By cdorman Date 07-01-2021 Time 15:12 Sent To  
Notes
2021-07-02 15:14:55.00000SHEET PV-04 & PV-05: CHANGE PV DISCONNECT OVERCURRENT
 DEVICE TO 50 AMP. 60A OVERCURRENT PROTECTION NOT
 APPROVED FOR #8 CU WITH 75 DEGREE C TERMINALS.
 PROVIDE VALUATION FOR PERMIT APPLICATION.