Plan Review Details - Permit 21060083
Plan Review Stops For Permit 21060083
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 06-11-2021 Cont ID  
Sent By cdorman Date 06-11-2021 Time 13:57 Rev Time 0.00
Received By cdorman Date 06-07-2021 Time 10:51 Sent To  
Notes
2021-06-07 10:52:29.00000REVISED PLANS
  

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 06-02-2021 Cont ID  
Sent By cdorman Date 06-02-2021 Time 14:22 Rev Time 0.00
Received By cdorman Date 06-02-2021 Time 12:32 Sent To  
Notes
2021-06-02 14:22:50.00000SHEET E-01: #8 AWG CONDUCTORS BETWEEN SERVICE PANEL AND
 NEW LOAD CENTER DO NOT HAVE SUFFICIENT AMPACITY FOR PV
 SYSTEM. ALSO, PLEASE CLARIFY INTENT OF SHOWING A LOAD
 CENTER WITH A 70A MAIN PLUS A 70A PV BACKFED BREAKER.
 THIS INSTALLATION WOULD PROVIDE ADDITIONAL CIRCUIT
 BREAKER SPACES THAT COULD BE USED FOR FUTURE LOADS,
 THEREBY OVERLOADING THE BUSS. THE PV DISCONNECT SHOULD
 PROVIDE OVERCURRENT PROTECTION, CIRCUIT SPACES, AND A
 DISCONNECTING MEANS FOR THE PV SYSTEM ONLY.