Plan Review Stops For Permit 21050813
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 06-07-2021 Cont ID  
Sent By cdorman Date 06-07-2021 Time 14:59 Rev Time 0.00
Received By cdorman Date 06-07-2021 Time 14:59 Sent To  
Notes
***NONE***

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 05-26-2021 Cont ID  
Sent By cdorman Date 05-26-2021 Time 16:21 Rev Time 0.00
Received By cdorman Date 05-26-2021 Time 08:12 Sent To  
Notes
2021-05-26 16:20:57.00000SHEET PV 4.0: #3 THWN CONDUCTORS INDENTIFIED AS "F" AND
 "E" DO NOT HAVE CORRECT OVERCURRENT PROTECTION. PROTECT
 AT MAXIMUM 100 AMPS OR REPLACE CONDUCTORS WITH 150 AMP
 RATED TO MATCH OVERCURRENT PROTECTION SHOWN.
 SYSTEM NOT RECOGNIZED AS A "STAND-ALONE SYSTEM" PER
 ARTICLE 710, SINCE LOADS IN BACKUP PANEL CAN BE
 SUPPLIED BY UTILITY.