Plan Review Details - Permit 21050153
Plan Review Stops For Permit 21050153
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 05-07-2021 Cont ID  
Sent By cdorman Date 05-07-2021 Time 16:00 Rev Time 0.00
Received By cdorman Date 05-06-2021 Time 07:50 Sent To  
Notes
2021-05-07 16:00:00.00000SHEET PV-06: PLANS SHOW PV OVERCURRENT DEVICE IN
 EXISTING 100A LOADCENTER, NOT APPROVED WITH BUSS
 RATING. SHOW OVERCURRENT PROTECTION IN PV DISCONNECT
 ONLY. ALL ASPECTS OF ONE-LINE DIAGRAM MUST CLEARLY AND
 CONSISTENTLY INDICATE THE POINT OF CONNECTION AND THE
 LOCATION OF THE OVERCURRENT PROTECTION. PV DISCONNECT
 FOR SUPPLY-SIDE TAP MUST BE NO MORE THAN TEN FEET FROM
 TAP, AND SHOULD BE INDICATED ON DRAWINGS.