Plan Review Details - Permit 21050038
Plan Review Stops For Permit 21050038
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 4 Status A Date 06-15-2021 Cont ID  
Sent By cdorman Date 06-15-2021 Time 13:08 Rev Time 0.00
Received By cdorman Date 06-15-2021 Time 10:20 Sent To  
Notes
2021-06-15 10:20:33.00000REVISED PLANS EXPRESSPERMITTING@GMAIL.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 3 Status D Date 06-11-2021 Cont ID  
Sent By cdorman Date 06-11-2021 Time 14:11 Rev Time 0.00
Received By cdorman Date 06-10-2021 Time 16:00 Sent To  
Notes
2021-06-11 14:11:13.00000REVISED PLANS, REVIEW INTAKE 6/11/21: ONE-LINE DIAGRAM
 IS INCONSISTENT IN IDENTIFYING MICROINVERTERS. TOP OF
 SHEET SPECIFIES IQ7-60; INVERTER RATING CHART SPECIFIES
 IQ7PLUS-72. REVISED DRAWING TO ACCURATELY AND
 CONSISTENTLY IDENTIFY INTENDED COMPONENT.

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 05-11-2021 Cont ID  
Sent By cdorman Date 05-11-2021 Time 08:13 Rev Time 0.00
Received By cdorman Date 05-05-2021 Time 13:18 Sent To  
Notes
2021-05-05 13:19:12.00000AMANDA@EXPRESSPERMITSLLC.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 05-04-2021 Cont ID  
Sent By cdorman Date 05-04-2021 Time 16:43 Rev Time 0.00
Received By cdorman Date 05-03-2021 Time 15:29 Sent To  
Notes
2021-05-04 16:42:33.00000CONDUCTORS BETWEEN COMBINER PANEL AND PV DISCONNECT,
 AND BETWEEN PV DISCONNECT AND SUPPLY SIDE TAP, MUST
 HAVE A MINIMUM AMPACITY OF 104 @ 75 DEGREES C. USE
 MINIMUM #2 THWN COPPER.
2021-05-03 15:30:05.00000DROPPED OFF