Plan Review Details - Permit 21040876
Plan Review Stops For Permit 21040876
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status C Date 05-04-2021 Cont ID  
Sent By cdorman Date 05-04-2021 Time 15:44 Rev Time 0.00
Received By cdorman Date 04-30-2021 Time 11:14 Sent To  
Notes
2021-05-04 15:44:36.00000CONDITIONAL APPROVAL: REFER TO SHEET PV-2. PV
 DISCONNECT MUST CONTAIN 45A FUSES, NOT 40A. SYSTEM
 INCORPORATES (33) IQ7-60 INVERTERS @ 1 AMP EACH. 33 X 1
 X 1.25 = 41.25 MINIMUM REQUIRED AMPACITY.