Plan Review Stops For Permit 21040789
Review Stop BLDREN REISSUANCE BUILDING PERMIT
Rev No 1 Status A Date 05-06-2021 Cont ID  
Sent By cdorman Date 05-06-2021 Time 15:20 Rev Time 0.00
Received By cdorman Date 05-04-2021 Time 16:35 Sent To  
Notes
2021-05-24 14:56:01.00000*NO ELECTRONIC APPROVED SET.. HARD COPY SETS APPROVED
 WITH APPLICAITON IN 3RD DRAWER, READY TO BE PAYED FOR
 AND PICKED UP.
2021-05-07 14:42:49.00000NOT SURE WHY, BUT WE RECEIVED A SET OF REVISED PLANS
 AND A SOLAR APP VIA FEDEX 05/07/2021
2021-05-04 16:36:16.00000JOET@OURSOLARBEAR.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By cshackel Date 04-27-2021 Time 09:53 Sent To  
Notes
2021-04-27 15:58:30.000001] PROVIDE SOLAR APPLICATION, NOT RESIDENTIAL BUILDING
 APPLICATION.
 2] SHEET E-1: IQ7-72-2-US MICROINVERTERS HAVE A MAXIMUM
 CONTINUOUS OUTPUT CURRENT OF 1.21 AMPS @ 240 VOLTS.
 REVISE ONE-LINE AND ALL NOTES TO REFLECT THE COMBINED
 INVERTER CURRENT OUTPUT. ASSUMING THE USE OF THESE
 MICROINVERTERS, MINIMUM FUSING SHOULD BE 45 AMPS (27 X
 1.21 X 1.25, NEXT SIZE O/C PROTECTION) AND RATED OUTPUT
 AC CURRENT LABEL SHOULD SHOW 33 AMPS. IN ANY CASE,
 COMBINED INVERTER OUTPUTS, LABELING, CONDUCTOR SIZES,
 AND OVERCURRENT PROTECTION MUST BE CONSISTENT.
2021-04-27 09:54:21.00000PERMIT PACKAGE MAILED IN. . FILLED OUT WRONG PERMIT
 APP, FILLED OUT RESIDENTIAL APP, EMAILED THE COMPANY
 THE SOLAR APP TO FILL OUT, HAVE NOT RECEIVED IT.