Plan Review Details - Permit 21040657
Plan Review Stops For Permit 21040657
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 04-29-2021 Cont ID  
Sent By cdorman Date 04-29-2021 Time 14:59 Rev Time 0.00
Received By cdorman Date 04-26-2021 Time 12:44 Sent To  
Notes
2021-04-26 12:45:42.00000AMANDA@EXPRESSPERMITSLLC.COM
2021-04-26 12:44:41.00000REVISION
  

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By cshackel Date 04-22-2021 Time 09:03 Sent To  
Notes
2021-04-23 14:53:02.00000ONE-LINE DIAGRAM: IF USING LINE-SIDE TAP, GROUNDED
 CONDUCTOR BETWEEN PV DISCONNECT AND TAP MUST BE MINIMUM
 #8 CU. SEE TABLE 250.102 (C)(1).
2021-04-22 09:03:43.00000DROPPED OFF