Plan Review Details - Permit 21040619
Plan Review Stops For Permit 21040619
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 05-10-2021 Cont ID  
Sent By cdorman Date 05-10-2021 Time 08:23 Rev Time 0.00
Received By cdorman Date 05-05-2021 Time 11:14 Sent To  
Notes
2021-05-05 11:14:45.00000KHADLEY@FREEDOMFOREVER.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 04-23-2021 Cont ID  
Sent By cdorman Date 04-23-2021 Time 13:41 Rev Time 0.00
Received By cdorman Date 04-21-2021 Time 10:14 Sent To  
Notes
2021-04-23 13:41:24.000001] SHEET PV 4: #8 CU NOT APPROVED BETWEEN INVERTER AND
 PV DISCONNECT; MINIMUM CONDUCTOR AMPACITY @ 75 DEGREES
 C = 52.5 AMPS. USE MIN #6 CU.
 2] SPEC SHEET FOR MODULES DOES NOT MATCH MODULE
 SPECIFIED ON PLANS.
2021-04-21 10:17:47.00000EMAILED IN BY KHADLEY@FREEDOMFOREVER.COM