Plan Review Details - Permit 21040273
Plan Review Stops For Permit 21040273
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 4 Status A Date 04-20-2021 Cont ID  
Sent By cdorman Date 04-20-2021 Time 14:21 Rev Time 0.00
Received By cdorman Date 04-20-2021 Time 11:40 Sent To  
Notes
***NONE***

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 3 Status D Date 04-19-2021 Cont ID  
Sent By cdorman Date 04-19-2021 Time 08:49 Rev Time 0.00
Received By cdorman Date 04-16-2021 Time 11:47 Sent To  
Notes
2021-04-19 08:49:19.000001] CONDUCTORS BETWEEN COMBINER PANEL AND SERVICE MUST
 BE MINIMUM #8 CU. 310.15 (B)(16), 75 DEGREE COLUMN FOR
 #10 = 35 AMPS. MINIMUM AMPACITY REQUIRED FOR THIS
 SYSTEM IS 36.25. SEE ALSO 240.4 (D)(7), REFERENCING
 240.4 (G).
 2] CHANGE GROUNDED CONDUCTOR BETWEEN SUPPLY-SIDE TAP
 AND PV DISCONNECT TO MINIMUM #8 CU. TABLE 250.102
 (C)(1).

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status Z Date 04-13-2021 Cont ID  
Sent By cdorman Date 04-13-2021 Time 15:17 Rev Time 0.00
Received By cdorman Date 04-13-2021 Time 13:51 Sent To  
Notes
***NONE***

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 04-12-2021 Cont ID  
Sent By cdorman Date 04-12-2021 Time 16:21 Rev Time 0.00
Received By cdorman Date 04-09-2021 Time 16:34 Sent To  
Notes
2021-04-12 16:20:59.00000ELECTRICAL SHEET: 125% OF COMBINED INVERTER OUTPUT PLUS
 MAIN BREAKER RATING EXCEEDS 120% OF BUSS RATING IN
 PANEL. (29A X 1.25) + 150A = 186.25A. BUSS RATING OF
 150A X 1.20 = 180A.
 IF USING BACKFED CIRCUIT BREAKER, MUST COMPLY WITH
 705.12 (B)(2)(3)(B).
 VERIFY 200A BUSS WITH 150A MAIN, OR USE SUPPLY-SIDE TAP
 WITH APPROPRIATE OVERCURRENT PROTECTION.