Plan Review Details - Permit 21040028
Plan Review Stops For Permit 21040028
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 4 Status A Date 04-20-2021 Cont ID  
Sent By cdorman Date 04-20-2021 Time 14:34 Rev Time 0.00
Received By cdorman Date 04-20-2021 Time 11:39 Sent To  
Notes
***NONE***

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 3 Status D Date 04-19-2021 Cont ID  
Sent By cdorman Date 04-19-2021 Time 08:33 Rev Time 0.00
Received By cdorman Date 04-16-2021 Time 11:51 Sent To  
Notes
2021-04-19 08:32:58.00000SUPPLY-SIDE BONDING CONDUCTOR BETWEEN SERVICE AND PV
 DISCONNECT STILL SHOWN AS #10; MUST BE MIN #8. SEE NOTE
 2 FROM PREVIOUS REVIEW.
2021-04-16 11:52:09.00000EXPRESSPERMITTING@GMAIL.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status D Date 04-14-2021 Cont ID  
Sent By cdorman Date 04-14-2021 Time 13:54 Rev Time 0.00
Received By cdorman Date 04-13-2021 Time   Sent To  
Notes
2021-04-14 13:54:37.0000004/13/2021 ELECTRICAL SHEET, REVISION 1:
 1] QUANTITY OF MODULES SHOWN ON ONE LINE DIAGRAM DOES
 NOT MATCH QUANTITY SHOWN ON PAGE SUMMARY (TOP CENTER OF
 SHEET)
 2] THE GROUNDED CONDUCTOR BETWEEN THE SERVICE AND THE
 PV DISCONNECT MUST BE MINIMUM #8 CU IF USING A
 SUPPLY SIDE TAP. SEE TABLE 250.102 (C)(1) FOR MINIMUM
 SIZE OF SUPPLY SIDE BONDING AND GROUNDED CONDUCTORS.
  

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 04-05-2021 Cont ID  
Sent By cdorman Date 04-05-2021 Time 08:17 Rev Time 0.00
Received By cdorman Date 04-01-2021 Time 16:07 Sent To  
Notes
2021-04-05 08:17:29.00000ONE-LINE DIAGRAM: OVERCURRENT PROTECTION IN PV
 DISCONNECT DOES NOT CORRESPOND WITH CONDUCTOR SIZE.