Plan Review Details - Permit 21040018
Plan Review Stops For Permit 21040018
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 04-08-2021 Cont ID  
Sent By cdorman Date 04-08-2021 Time 15:25 Rev Time 0.00
Received By cdorman Date 04-05-2021 Time 12:08 Sent To  
Notes
2021-04-05 12:13:45.00000SEABREEZEPERMIT@GMAIL.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 04-01-2021 Cont ID  
Sent By cdorman Date 04-01-2021 Time 16:28 Rev Time 0.00
Received By cdorman Date 04-01-2021 Time 13:42 Sent To  
Notes
2021-04-01 16:28:14.00000SHEET E-1: #10 THWN-2 CONDUCTORS FROM SUPPLY SIDE TAP
 TO PV DISCONNECT, AND FROM PV DISCONNECT TO COMBINER,
 CANNOT BE PROTECTED AT 40 AMPS; EXCEEDS TEMPERATURE
 RATING OF TERMINALS, SEE 110.14 (C)(1) AND TABLE 310.15
 (B)(16). USE 30A MAXIMUM OVERCURRENT PROTECTION OR
 INCREASE CONDUCTOR SIZE.