Plan Review Details - Permit 21030904
Plan Review Stops For Permit 21030904
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 03-31-2021 Cont ID  
Sent By cdorman Date 03-31-2021 Time 14:57 Rev Time 0.00
Received By cdorman Date 03-31-2021 Time 08:55 Sent To  
Notes
2021-03-31 08:56:15.00000EMAILED REVISED PLAN NICOLE@EXPRESSPERMITSLLC.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 03-25-2021 Cont ID  
Sent By cdorman Date 03-25-2021 Time 14:24 Rev Time 0.00
Received By cdorman Date 03-25-2021 Time 12:55 Sent To  
Notes
2021-03-25 14:24:44.000001] #6 THWN-2 CONDUCTORS BETWEEN COMBINER PANEL AND
 SERVICE ARE UNDERSIZED FOR 125% OF COMBINED INVERTER
 OUTPUTS. REPLACE WITH MINIMUM #4.
 2] INCLUDE RAPID SHUTDOWN GRAPHIC LABEL IDENTIFIED IN
 690.56.
 3] INCLUDED RAPID SHUTDOWN SWITCH IDENTIFICATION LABEL
 PER 690.56.