Plan Review Stops For Permit 21020832
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 02-25-2021 Cont ID  
Sent By cdorman Date 02-25-2021 Time 15:55 Rev Time 0.00
Received By cdorman Date 02-25-2021 Time 12:54 Sent To  
Notes
2021-02-25 15:55:38.000001] PROVIDE COMPLETE LABEL IDENTIFICATION SHEET SHOWING
 ALL REQUIRED LABELING PER ARTICLES 690 & 705.
 2] ONE-LINE DIAGRAM SHOWS PV DISCONNECT AS 40 AMP, WITH
 50 AMP FUSES. PLEASE CORRECT.