Plan Review Details - Permit 21010099
Plan Review Stops For Permit 21010099
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 02-02-2021 Cont ID  
Sent By cdorman Date 02-02-2021 Time 15:21 Rev Time 0.00
Received By cdorman Date 02-02-2021 Time 08:40 Sent To  
Notes
2021-02-02 08:40:44.00000REVISED PLANS RECEIVED 02/02/21

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 01-19-2021 Cont ID  
Sent By cdorman Date 01-19-2021 Time 15:09 Rev Time 0.00
Received By cdorman Date 01-06-2021 Time 15:52 Sent To  
Notes
2021-01-19 15:09:31.000001] SHEET PV-3: WIRE TAG #3 SHOWS 1" PVC CONDUIT
 SPANNING APPROXIMATELY EIGHT FEET THROUGH OPEN AIR.
 TABLE 352.30 REQUIRES MAXIMUM SUPPORT SPACING OF THREE
 FEET. USE ALTERNATE RACEWAY OR SPECIFY SUPPORT MEANS TO
 COMPLY WITH THIS SECTION.
 2] SHEET PV-3.2: RAPID SHUTDOWN COMPLIANCE LABEL MUST
 BE PER FIGURE 690.56 (C)(1)(A)
 PER FL ADMIN CODE RULES 61G4-15.021(3)(D), ELECTRICAL
 WORK IS TO BE PERMITTED AND PERFORMED BY A LICENSED
 ELECTRICAL CONTRACTOR. THE SCOPE OF WORK OF A SOLAR
 CONTRACTOR IS LIMITED TO THAT ON THE PV SIDE OF THE
 POWER CONDITIONING UNIT.
2021-01-15 16:26:52.00000ORIGINAL PLANS WERE UNDER OLD CODE, RESUBMITTED PLANS
 UNDER 2020FBC, RECEIVED IN MAIL 01-15-2021.
2021-01-06 15:52:28.00000MAILED IN