Plan Review Details - Permit 20120701
Plan Review Stops For Permit 20120701
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 01-07-2021 Cont ID  
Sent By cdorman Date 01-07-2021 Time 14:33 Rev Time 0.00
Received By cdorman Date 01-07-2021 Time 14:33 Sent To  
Notes
2021-01-07 14:33:39.00000NEW PLANS REC'D.

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 12-29-2020 Cont ID  
Sent By cdorman Date 12-29-2020 Time 16:04 Rev Time 0.00
Received By cdorman Date 12-29-2020 Time 14:52 Sent To  
Notes
2020-12-29 16:04:51.000001] SHEETS A-1, A-2, AND A-3 MUST SHOW COMPLIANCE WITH
 FLORIDA FIRE PREVENTION CODE 11.12.2.2.2. MINIMUM THREE
 FOOT SEPARATION FROM ROOF RIDGE APPLIES.
 2] PROVIDE SPECIFICATION PAGE(S) FOR ENPHASE AC
 COMBINER PANEL.
 3] SHEET E-4 MUST SHOW NEUTRAL-TO-CASE BOND IN PV
 DISCONNECT FOR SUPPLY-SIDE PV CONNECTION. THE SEPARATE
 EQUIPMENT GROUNDING CONDUCTOR BETWEEN THE PV DISCONNECT
 AND THE SUPPLY-SIDE TAP SHOULD BE REMOVED.
 EMAILED THIS REPORT TO CONTRACTOR'S EMAIL-OF-RECORD
 12/29/20; WAS RETURNED AS UNDELIVERABLE.
  