Plan Review Stops For Permit 20120081
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 12-09-2020 Cont ID  
Sent By cdorman Date 12-09-2020 Time 14:39 Rev Time 0.00
Received By cdorman Date 12-07-2020 Time 14:38 Sent To  
Notes
***NONE***

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 12-04-2020 Cont ID  
Sent By cdorman Date 12-04-2020 Time 15:17 Rev Time 0.00
Received By cdorman Date 12-03-2020 Time 13:30 Sent To  
Notes
2020-12-04 15:16:58.000001] PV DISCONNECT RATING MUST BE NOT LESS THAN 125 % OF
 COMBINED INVERTER OUTPUT
 2] SHOW RATINGS OF OVERCURRENT DEVICES IN COMBINER
 PANEL; MUST BE NOT LESS THAN 125% OF INVERTER OUTPUT
 3] PROVIDE PE SEAL FOR PROPOSED GROUND-MOUNT DESIGN,
 REFERENCING COMPLIANCE WITH 6TH EDITION FLORIDA
 BUILDING CODE