Plan Review Details - Permit 20100028
Plan Review Stops For Permit 20100028
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 3 Status A Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By cdorman Date 10-09-2020 Time 13:35 Sent To  
Notes
***NONE***

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status D Date 10-06-2020 Cont ID  
Sent By cdorman Date 10-06-2020 Time 14:31 Rev Time 0.00
Received By cdorman Date 10-06-2020 Time 14:30 Sent To  
Notes
2020-10-06 14:31:00.00000NEW ONE-LINE DIAGRAM RECEIVED; SAME DEFICIENCIES

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 10-02-2020 Cont ID HC04350
Sent By cdorman Date 10-02-2020 Time 09:16 Rev Time 0.00
Received By cdorman Date 10-01-2020 Time 14:22 Sent To  
Notes
2020-10-02 09:16:12.00000FSEC CERTIFICATION AND TITLE ON ONE-LINE DIAGRAM
 INDICATE IQ7 INVERTERS; MICROINVERTER SPECIFICATION ON
 ONE-LINE SHOWS CURRENT PARAMETER FOR IQ7+ INVERTER
 (1.21 AMPS). PLEASE CLARIFY; INVERTER DATA MUST BE
 CONSISTENT THROUGHOUT PLAN.
 SHOW QUANTITY OF MODULES PER STRING ON ONE-LINE
 DIAGRAM.
  
 AC CURRENT OUTPUT LABEL MUST EXACTLY MATCH TOTAL SYSTEM
 OUTPUT WITHOUT ANY DEMAND ADJUSTMENTS.

Copyright © 2008 – THE PLUS SERIES ® – All Rights Reserved