Plan Review Details - Permit 20100027
Plan Review Stops For Permit 20100027
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 3 Status A Date 10-09-2020 Cont ID  
Sent By cdorman Date 10-09-2020 Time 13:24 Rev Time 0.00
Received By cdorman Date 10-09-2020 Time 13:24 Sent To  
Notes
***NONE***

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status D Date 10-06-2020 Cont ID  
Sent By cdorman Date 10-06-2020 Time 14:28 Rev Time 0.00
Received By cdorman Date 10-06-2020 Time 14:27 Sent To  
Notes
2020-10-06 14:28:25.00000RECEIVED NEW ONE-LINE DIAGRAM; SAME DEFICIENCIES.

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 10-02-2020 Cont ID HC04250
Sent By cdorman Date 10-02-2020 Time 09:08 Rev Time 0.00
Received By cdorman Date 10-01-2020 Time 14:15 Sent To  
Notes
2020-10-02 09:08:41.00000FSEC CERTIFICATE AND TITLE ON ONE-LINE DIAGRAM INDICATE
 IQ7 INVERTERS; MICROINVERTER SPECIFICATION ON ONE-LINE
 SHOWS CURRENT PARAMETER FOR IQ7+ INVERTER (1.21 AMPS).
 PLEASE CLARIFY; INVERTER DATA MUST BE CONSISTENT
 THROUGHOUT PLAN.
  
 AC CURRENT OUTPUT LABEL MUST EXACTLY MATCH TOTAL SYSTEM
 OUTPUT WITHOUT ANY DEMAND ADJUSTMENTS.